Contribution of variable-speed pump hydro storage for power system dynamic performance

Thumbnail Image
Date
2017
Authors
Bernardo Silva
Carlos Moreira
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
This paper presents the study of variable-speed Pump Storage Powerplant (PSP) in the Portuguese power system. It evaluates the progressive integration in three major locations and compares the power system performance following a severe fault event with consequent disconnection of non-Fault Ride-through (FRT) compliant Wind Farms (WF). To achieve such objective, a frequency responsive model was developed in PSS/E and was further used to substitute existing fixed-speed PSP. The results allow identifying a clear enhancement on the power system performance by the presence of frequency responsive variable-speed PSP, especially for the scenario presented, with high level of renewables integration. © Published under licence by IOP Publishing Ltd.