Sequence networks to the calculation of two-simultaneous faults at the same location

dc.contributor.author Moura,AP en
dc.contributor.author João Peças Lopes en
dc.contributor.author de Moura,AAF en
dc.date.accessioned 2018-01-13T11:08:01Z
dc.date.available 2018-01-13T11:08:01Z
dc.date.issued 2015 en
dc.description.abstract The system of symmetrical components (012-system) can be used to simulate symmetrical and asymmetrical operation of power systems. However, the classical literature of Power Systems Analysis does not present one equivalent circuit in 012-system to two-simultaneous faults where there are a single-line-to-ground fault and a bolted line-to-line fault. This paper presents the equations and the new equivalent circuit mentioned. In addition, we present a comparison of results between the proposed approach and the output of the commercial software ANAFAS, which validates the methodology. We find evidence that the new equivalent circuit developed can substitute the equivalent circuits used to calculate a single line-to-ground fault and a bolted line-to-line fault. en
dc.identifier.uri http://repositorio.inesctec.pt/handle/123456789/6009
dc.identifier.uri http://dx.doi.org/10.1016/j.ijepes.2015.01.037 en
dc.language eng en
dc.relation 1103 en
dc.rights info:eu-repo/semantics/openAccess en
dc.title Sequence networks to the calculation of two-simultaneous faults at the same location en
dc.type article en
dc.type Publication en
Files
Original bundle
Now showing 1 - 1 of 1
Thumbnail Image
Name:
P-00A-7D0.pdf
Size:
1.09 MB
Format:
Adobe Portable Document Format
Description: